Hard Drawn Aluminum Wires are manufactured from EC Grade 1350 / 1370 aluminum rods through a cold-drawing process without intermediate annealing.
This process increases the tensile strength while maintaining high electrical conductivity, making them ideal for electrical conductors, aerial wires, braiding, and cable manufacturing.
These wires are used for overhead power lines, mechanical reinforcement strands, screening, and binding where both conductivity and strength are required.
Main Features
Produced from EC Grade Aluminum 99.7–99.8 % purity (1350 / 1370)
High tensile strength: 130–160 MPa
Conductivity: ≥ 61 % IACS
Density: 2.703 g/cm³
Smooth, bright surface finish
Manufactured according to EN 1715 / ASTM B233 / IEC 60182 / TS 1370
Technical Data – Typical Dimensions
Hard Drawn Aluminum Wires
| Nominal Dia (mm) | Cross Section (mm²) | Approx. Mass (kg/km) | Tensile Strength (MPa) | Conductivity (% IACS) | Typical Applications |
|---|---|---|---|---|---|
| 1.20 | 1.13 | 3.06 | 150–160 | ≥ 61 | Braiding / Screening |
| 1.40 | 1.54 | 4.18 | 150–160 | ≥ 61 | Control Cable Conductors |
| 1.80 | 2.54 | 6.89 | 145–155 | ≥ 61 | Aerial Drop Wires |
| 2.00 | 3.14 | 8.52 | 145–155 | ≥ 61 | Binding Wires |
| 2.40 | 4.52 | 12.3 | 140–150 | ≥ 61 | Conductor Stranding |
| 2.60 | 5.31 | 14.4 | 140–150 | ≥ 61 | Low Voltage Cables |
| 3.00 | 7.07 | 19.2 | 135–145 | ≥ 61 | Overhead Conductors |
| 3.20 | 8.04 | 21.9 | 135–145 | ≥ 61 | Aerial Bundled Cables (ABC) |
| 3.80 | 11.34 | 30.8 | 130–140 | ≥ 61 | MV Conductor Core Wires |
| 4.10 | 13.20 | 35.8 | 130–140 | ≥ 61 | Power Cable Stranding |
| 4.50 | 15.90 | 43.1 | 130–140 | ≥ 61 | Large Cable Conductors |
| 5.00 | 19.63 | 53.2 | 125–135 | ≥ 61 | Transmission Conductors |
Other diameters available upon request (1.0 – 5.0 mm range).
Standards
EN 1715 / EN 50182 / IEC 60182 – Conductors for Overhead Lines
ASTM B233 – Aluminum 1350 Wire, Hard-Drawn
TS 1370 – Sert Çekilmiş Alüminyum Teller (Türk Standardı)
RoHS / REACH compliant
Applications
Conductors for overhead lines (AAC, AAAC, ACSR stranding wires)
Binding and screening applications in power cables
Braiding, grounding, and mechanical connections
Used as raw material for aluminum stranded conductors










Reviews