ACSR conductors consist of a core of galvanized steel wires surrounded by one or more layers of EC Grade 1350 or 1370 aluminum wires concentrically stranded.
This combination provides excellent conductivity from aluminum and high mechanical strength from the steel core.
They are widely used for overhead transmission and distribution lines, especially where long spans, high tension, or severe climatic conditions exist.
Main Features
High electrical conductivity (≥ 61 % IACS)
Superior tensile strength due to galvanized steel core
Excellent corrosion resistance (Class A/B/C galvanization)
Suitable for LV / MV / HV overhead lines
Manufactured in compliance with EN 50182 / IEC 61089
Technical Data – Typical Dimensions
ACSR – Aluminum Conductor Steel Reinforced (According to EN 50182 / IEC 61089)
| Type (EN 50182) | Trade Name | Stranding (Al/St) | Aluminium Area (mm²) | Steel Area (mm²) | Total Area (mm²) | Overall Dia. (mm) | Approx. Weight (kg/km) | Rated Tensile Strength (daN) | DC Resistance (Ω/km 20 °C) | Current (A) |
|---|---|---|---|---|---|---|---|---|---|---|
| ACSR 25/4 | Raven | 6 Al + 1 St | 24.8 | 4.13 | 28.9 | 6.75 | 84 | 1 180 | 1.180 | 145 |
| ACSR 35/6 | Pigeon | 6 Al + 1 St | 34.4 | 5.73 | 40.1 | 8.10 | 115 | 1 560 | 0.857 | 185 |
| ACSR 50/8 | Drake | 6 Al + 1 St | 49.4 | 8.22 | 57.6 | 9.45 | 155 | 2 050 | 0.598 | 230 |
| ACSR 70/11 | Swan | 6 Al + 1 St | 68.4 | 11.39 | 79.8 | 10.80 | 205 | 2 620 | 0.433 | 280 |
| ACSR 95/15 | Rail | 6 Al + 1 St | 93.3 | 15.52 | 108.8 | 12.30 | 260 | 3 320 | 0.320 | 340 |
| ACSR 120/20 | Finch | 6 Al + 1 St | 118.6 | 19.72 | 138.3 | 13.50 | 315 | 3 980 | 0.265 | 390 |
| ACSR 150/25 | Drake(H) | 6 Al + 1 St | 147.3 | 24.49 | 171.8 | 14.85 | 380 | 4 690 | 0.214 | 435 |
| ACSR 185/30 | Peacock | 6 Al + 1 St | 182.5 | 30.33 | 212.8 | 16.20 | 465 | 5 500 | 0.176 | 480 |
| ACSR 240/40 | Lynx | 6 Al + 1 St | 240.1 | 39.87 | 279.9 | 18.00 | 610 | 6 760 | 0.134 | 540 |
| ACSR 300/50 | Panther | 6 Al + 1 St | 297.3 | 49.84 | 347.1 | 20.10 | 745 | 7 980 | 0.108 | 590 |
| ACSR 400/65 | Zebra | 6 Al + 1 St | 396.5 | 65.48 | 461.9 | 22.65 | 990 | 9 840 | 0.081 | 665 |
| ACSR 500/85 | Moose | 6 Al + 1 St | 496.3 | 83.42 | 579.7 | 25.35 | 1 230 | 11 450 | 0.065 | 740 |
| ACSR 630/100 | Lapwing | 6 Al + 1 St | 620.6 | 99.35 | 719.9 | 28.50 | 1 500 | 13 100 | 0.053 | 830 |
| ACSR 800/125 | Falcon | 6 Al + 1 St | 792.4 | 123.7 | 916.1 | 31.50 | 1 820 | 14 900 | 0.041 | 920 |
| ACSR 1000/150 | Eagle | 6 Al + 1 St | 989.5 | 148.4 | 1 137.9 | 34.50 | 2 200 | 16 800 | 0.033 | 1 020 |
| ACSR 1250/190 | Pelican | 6 Al + 1 St | 1 244.0 | 189.6 | 1 433.6 | 38.40 | 2 690 | 19 500 | 0.026 | 1 120 |
Standards
EN 50182 / IEC 61089 – Overhead electrical conductors (European and International Standard)
TS EN 50182 / TS IEC 61089 – Turkish Standard equivalent
ASTM B232 / B232M – American reference (code names)
BS 215 Part 2 – British Standard
DIN 48204 – German Standard
Applications
Overhead power transmission and distribution lines
Long-span installations and river crossings
High wind or ice load areas
Mountainous or coastal regions










Reviews